Common fault maintenance and maintenance precautions for power distribution cabinets

Distribution cabinet common fault maintenance and maintenance precautions The distribution box is also called the distribution cabinet, which is the general name of the motor control center.


Distribution cabinet common fault maintenance and maintenance precautions The distribution box is also called the distribution cabinet, which is the general name of the motor control center. The distribution box is to assemble the switchgear, measuring instruments, protective appliances and auxiliary equipment in a closed or semi-enclosed metal cabinet or screen according to the requirements of electrical wiring, forming a low-voltage power distribution device. The distribution box has the characteristics of small size, easy installation, special technical performance, fixed position, configuration function, not limited by site, relatively common application, stable operation, high space utilization, less land occupation and environmental protection effect.

Distribution cabinet maintenance

1. The circuit breaker cannot be closed 1. Press the closing button, and the closing coil is electric but does not operate - replace the undervoltage coil; 2. Poor contact of the closing button - replace the closing button; 3. The melt core (insurance) of the control loop burns out - replace the melt core; 4. There is no energy storage in the circuit breaker - check that the motor voltage must be greater than 85%; 5. The voltage of the closing solenoid is too small - the voltage of the closing solenoid must be greater than 85%; 6. Closing solenoid is damaged - replace the closing solenoid; 7. Poor contact of the secondary circuit of the drawer circuit breaker - shake out the drawer circuit breaker, and then shake it back to the connected position to check whether the secondary circuit is connected reliably; 8. The 10,000-turn switch is in the stop position - turn the switch to the power transmission position.

2. The main switch of the incoming cabinet cannot be opened1, and the opening button is in poor contact - replace the opening button; 2. The opening coil burns out - replace the opening coil.

3. The main metering reactive power meter reverses or does not rotate 1, the power factor of capacitance compensation is high - adjust the capacitance compensation to 0.92-0.97; 2. The phase sequence of the transformer incoming line is wrong - readjust the phase sequence; 3. The voltage and current circuit is normal - replace the reactive power meter.

Fourth, the capacitor cabinet can not be automatically switched 1, the current sampling signal line is not connected - connect the current sampling signal line; 2. Compensate for the burning out of the melt core of the controller - replace the melt core; 3. The voltage is high, and the controller displays overvoltage - adjust the overvoltage protection point; 4. The current is small, and the controller display is ahead - it can work automatically after increasing the current; 5. The capacitor cabinet compensator shows overvoltage - re-set the voltage value.

Fifth, the drawer outlet line electric energy meter does not rotate 1, the secondary plug-in contact is poor - readjust the secondary plug-in contact piece; 2. The current and voltage are normal - replace the electric energy meter.

 

Other dynamics


What is the inverter cabinet The role of the inverter cabinet

The inverter cabinet uses the inverter to drag the control cabinet of the power unit. Because of its good starting performance, speed regulation performance and energy-saving effect, it has become the current promoted power drag mode.


The control cabinet of the distribution box should be cleaned and maintained regularly

When the distribution box generator is working, the engineer personnel should concentrate their thoughts and operate cautiously when operating the distribution board. After the motor unit is started, it should be slowly accelerated manually by using the speed up switch of the power screen.


Common fault maintenance and maintenance precautions for power distribution cabinets

Distribution cabinet common fault maintenance and maintenance precautions The distribution box is also called the distribution cabinet, which is the general name of the motor control center.


How to wire the dual power transfer switch?

In the event of a power outage for any reason, and power cannot be restored within a short period of time, backup power must be activated.


Power system automation structure

Power system automation realizes automatic control, automatic scheduling and automatic management of electric energy production, transmission and management. The power system [1] is a complex and large-scale system with a wide geographical distribution, composed of power plants, substations, transmission and distribution networks, and users.


The reason for the heating up of the high-voltage switchgear when it is energized

After a brief familiarity with the high-voltage switchgear, and let's learn the reasons for the heating up of the high-voltage switchgear when it is energized, I don't know if you will be interested in it? We are dedicated to providing you with the best quality service, let's take a look.