CAST-RESIN BUSWAY
Cast-resin Busway
A fully sealed busway system for damp, dusty, and corrosive environments
Conductors are fully encapsulated in insulating cast resin to create a compact, void-free protective structure for basements, outdoor links, and demanding industrial environments.
Rated current
400–6300 A
Rated operational voltage
Up to 1000 V AC
Insulation system
Mineral-filled epoxy casting
Protection rating
IP68

Product Details
Features and Benefits
| Feature | Description |
|---|---|
| Fully sealed | Cast material encapsulates the conductors and minimizes internal voids, providing a structural basis for damp, dusty, and corrosive environments. |
| Mechanical protection | The continuous casting provides insulation and external protection where high structural integrity is required. |
| Adaptable routing | Straight, bend, and transition units can follow the site route; joint protection must be verified as part of the complete system. |
| Environmental suitability | Water resistance, corrosion resistance and outdoor suitability depend on the selected configuration and the applicable model’s type-test results. |
Technical Specifications
| Parameter | Specification |
|---|---|
| Rated current | 400–6300 A |
| Rated operational voltage Ue | Up to 1000 V AC |
| Rated insulation voltage Ui | 1000 V |
| Rated frequency | 50 / 60 Hz |
| Conductor | Copper; other options subject to project confirmation |
| Wiring system | 3P3W / 3P4W / 3P5W |
| Casting system | Epoxy resin with inorganic mineral filler |
| Short-time withstand current Icw | Up to 120 kA / 1 s* |
| Protection rating | IP68* |
| Standards | IEC 61439-1 / IEC 61439-6 |
* Marked values are design targets for selection. Confirm them for the applicable model, project configuration and test results.
Options and Configurations
| Configuration | Options and Details |
|---|---|
| Conductor | Copper / project-specific conductor |
| Surface | Natural cast finish / weather-resistant layer |
| Installation | Horizontal / vertical / outdoor link |
| Joint | Standard / enhanced-protection joint |
| Applications | Basements and underground spaces, Damp industrial environments, Outdoor power links, Dust-intensive production areas |
Related Products
Cast-resin Fire-resistant BuswayCast-resin Fire-resistant BuswayA critical-power system using a mineral casting for fire and environmental protectionView details
Compact Sandwich BuswayCompact Sandwich BuswayA compact low-voltage backbone for high-power-density distributionView details
NS-STrack Busway for Data CentersSelect tap-off positions along the track as racks are installed or expandedView details