CAST-RESIN FIRE-RESISTANT BUSWAY
Cast-resin Fire-resistant Busway
A critical-power system using a mineral casting for fire and environmental protection
Fire-resistant mineral filler and insulating resin fully encapsulate the conductors, combining void-free sealing with circuit-integrity design for underground transport, energy facilities, and important public buildings.
Rated current
400–5000 A
Rated operational voltage
Up to 1000 V AC
Protection rating
IP68
Fire endurance
Up to 180 min

Product Details
Features and Benefits
| Feature | Description |
|---|---|
| Void-free fire-resistant construction | The fire-resistant casting continuously encapsulates conductors, limiting paths for flame, smoke, and moisture ingress. |
| Environmental and fire boundaries | For high-protection and fire applications, joints, terminations, and supports must be included in complete-system testing. |
| Stable mechanical support | The heavy casting continuously supports the conductors; brackets and loads must be verified during detailed design. |
| Fire and ingress protection | The 180 min and IP68 values are design targets for selection. Confirm performance against the applicable model’s type-test results. |
Technical Specifications
| Parameter | Specification |
|---|---|
| Rated current | 400–5000 A |
| Rated operational voltage Ue | Up to 1000 V AC |
| Rated insulation voltage Ui | 1000 V |
| Rated frequency | 50 Hz |
| Conductor | Copper |
| Wiring system | 3P3W / 3P4W / 3P5W |
| Fire-resistant construction | Conductor insulation + fire-resistant mineral casting |
| Short-time withstand current Icw | Up to 120 kA / 1 s* |
| Fire endurance | Up to 180 min* |
| Standards | IEC 61439-1 / IEC 61439-6; fire requirements to project standard |
* Marked values are design targets for selection. Confirm them for the applicable model, project configuration and test results.
Options and Configurations
| Configuration | Options and Details |
|---|---|
| Fire rating | Configured to project fire curve and duration |
| Casting system | Standard mineral / enhanced fire-resistant system |
| Surface protection | Indoor / damp environment / enhanced outdoor |
| Installation | Horizontal / vertical / underground |
| Applications | Metro and tunnels, Energy and chemical facilities, Important public buildings, Fire and emergency power backbones |