NORTH Power Electric

COMPACT FIRE-RESISTANT BUSWAY

Compact Fire-resistant Busway

A compact backbone designed for power continuity under fire conditions

Adds multilayer fire-resistant insulation and a mechanical enclosure around a compact conductor assembly for fire-safety loads, emergency systems, and critical supply routes in occupied buildings.

Rated current

400–4000 A

Rated operational voltage

Up to 1000 V AC

Protection rating

IP66

Fire endurance

Configured to the project fire curve

NORTH compact fire-resistant busway with multilayer protective enclosure

Product Details

Features and Benefits

FeatureDescription
Multilayer fire protectionLayered fire-resistant insulation and a mechanical enclosure reduce direct heat exposure to conductor insulation.
Critical-load routesIntended for fire pumps, smoke control, emergency lighting, and similar critical loads; continuity duration must match system testing.
Compact installationRetains a low-profile compact arrangement for constrained fire-safety backbones and risers.
Fire and ingress protectionFire resistance and protection ratings are design targets for selection. Confirm performance against the applicable model’s system test results.

Technical Specifications

ParameterSpecification
Rated current400–4000 A
Rated operational voltage UeUp to 1000 V AC
Rated insulation voltage Ui1000 V
Rated frequency50 / 60 Hz
ConductorCopper
Wiring system3P3W / 3P4W / 3P5W
Fire-resistant constructionCompact conductors + multilayer fire-resistant insulation + metal enclosure
Short-time withstand current IcwUp to 80 kA / 1 s*
Protection ratingIP66*
StandardsIEC 61439-1 / IEC 61439-6; fire requirements to project standard

* Marked values are design targets for selection. Confirm them for the applicable model, project configuration and test results.

Options and Configurations

ConfigurationOptions and Details
Fire ratingDesigned to project continuity time and fire curve
Neutral100% N / 200% N
Protective enclosureStandard / enhanced fire-resistant layer
InstallationHorizontal / vertical / riser
ApplicationsFire-safety equipment supply, Critical hospital loads, Rail-transit emergency systems, High-rise fire-safety backbones