NORTH Power Electric

NS-G

Plug-in Busway for Data Centers

A low-profile busway for limited rack-top clearance or higher trunk currents

A continuous slot runs along the underside of the busway. A spring-loaded mechanism makes electrical contact and locks the tap-off box in place. Trunk ratings span 200-2000 A, with elbows, tee branches and monitoring options.

Trunk rated current

200-2000 A

Tap-off box rated current

63 / 128 A

Busway conductor

Copper

Protection rating

IP42

NS-G Plug-in Busway for Data Centers with a light gray feed box, low-profile trunk and three-outlet tap-off box

Product Details

Features and Benefits

FeatureDescription
Low-profile trunkSuited to data halls with limited rack-top clearance. Allow space for tap-off boxes, cable exits and servicing.
Spring-loaded plug-in connectionThe continuous underside slot allows tap-off boxes to be positioned along the run. A spring-loaded, self-locking mechanism secures each box.
Trunk ratings up to 2000 AThe range includes 1600 A and 2000 A trunk options that can be combined with elbows and tee branches.
Metering and temperature monitoringOptional smart metering and communications support temperature monitoring at the feed box and tap-off boxes. Joint monitoring is also available.

Technical Specifications

ParameterSpecification
Trunk rated current200-2000 A
Busway system3P + N + PE, copper conductors
Tap-off box rated current63 A or 128 A
Protection ratingIP42 (confirm for the selected straight sections, covers and interfaces)

Options and Configurations

ConfigurationOptions and Details
InstallationSingle-rod or double-rod hangers
RoutingStraight lengths, directional elbows, tee branches and integrated joint connectors
Tap-off box interfaces63 A with fixed or corded industrial sockets. 128 A with portable industrial sockets
Rack distributionOne box can supply three racks where rack loads allow
Monitoring and communicationsProject options include electrical parameter monitoring, temperature monitoring and wired or wireless communications
ApplicationsFinal distribution to data center rack rows, Data halls with limited rack-top clearance, Projects requiring higher trunk ratings or tee branches