Busway derating: which table should you use?

There is no public derating table for busways. GB/T 7251.6-2015 gives a correction formula and one reference point — the coefficient equals 1 at 35 °C ambient — and leaves the values to the manufacturer. With 1,600 A and a 70 K rise taken as illustrative, two hypothetical models return 1,576.9 A and 1,481.3 A at 45 °C; a separate aluminium busway series gives 0.90 at the same temperature. The three belong to two different objects and do not form a range for one unit.

Updated 2026.11.24·技术选型
Reading Note

This article is based on public sources and illustrative calculations. It does not constitute project-specific design, equipment-selection, or safety advice. Verify applicable standards, equipment parameters, and protection settings against actual project conditions.

The short answer

There is no public table to look up. Clauses 5.3.1 and 5.3.2 of GB/T 7251.6-2015 give a correction formula and one reference point — the temperature coefficient equals 1 at 35 °C ambient — and stop there. The coefficient values are declared by the manufacturer; the standard does not fix them.

With 1,600 A and a 70 K rise taken as illustrative, two hypothetical models return 1,576.9 A and 1,481.3 A at 45 °C: the first holds the rise at 70 K, the second holds the conductor at 105 °C. A separate aluminium busway series gives 0.90 at 45 °C, which scales to 1,440.0 A. The three belong to two different objects and cannot be lined up as a range for one unit: the first two differ in their assumption, the third is another product's declared value.

What conditions does the 1,600 A nameplate assume?

Clause 5.3.1 of GB/T 7251.6-2015 (Low-voltage switchgear and controlgear assemblies — Part 6: Busbar trunking systems (busways)) deals with installation first: rated current applies to a specific mounting direction, and for a short vertical section within a horizontal run — less than 3 m, for example — the effect of direction may be disregarded. Where the incoming unit is not at one end of the run, or where there is more than one, rated current is agreed between user and manufacturer. Temperature appears later in the same clause: the manufacturer may state rated current at different air temperatures, for example by I′ₙₐ = k₁ₐ · Iₙₐ, where k₁ₐ equals 1 at 35 °C ambient. Clause 5.3.2 gives the fuller form for a single circuit: I′ₙc = k₁c · k₂c · Iₙc, with k₂c an installation coefficient.

The operative word is "may". The standard authorises the manufacturer to declare these coefficients; it does not prescribe their values. Within the body of the standard, the only number attached to the temperature coefficient is that single point at 35 °C.

One point is widely confused: 35 °C is an illustrative reference point for the coefficient, not the only ambient at which the test may be run. Clause 10.10.2.3.4 of IEC 61439-6:2012 requires the ambient during that standard's temperature-rise test to lie between +10 °C and +40 °C, taken as the average of all measuring points. The clause constrains that test method; 35 °C can be the reference point of a coefficient table and can equally be the actual ambient of a given test. Outside that interval, capability has to come from the product's declaration and the applicable verification documents.

The reference chain matters too. Part 6 is built on GB 7251.1-2013: Clauses 4 and 5 both state that, except as noted, the corresponding clause of GB 7251.1-2013 applies. The 2023 edition of the general rules has been published and wholly replaces the 2013 edition, but 7251.6 still points at 2013, so quoting the temperature-rise limits of Table 6 requires saying which edition you mean.

Why do three different numbers come out?

Fix the reference point: nameplate 1,600 A, temperature rise 70 K (conductor at 105 °C). Both are illustrative values and describe no actual product.

SourceBasisImplied assumptionValue at 45 °CRatio to 1,600 A
Hypothetical model A: rise heldRise stays 70 K, conductor reaches 115 °CAssumes rise does not exceed 70 K1,576.9 A98.56%
Hypothetical model B: conductor heldConductor stays 105 °C, rise falls to 60 KAssumes conductor does not exceed 105 °C1,481.3 A92.58%
Other object: published manufacturer tableTable 8-3: 1.00 at 35 °C, 0.90 at 45 °CThe product's own declaration1,440.0 A90.00%
Three sources compared at 45 °C: model results of 1,576.9 A and 1,481.3 A, and a published table value of 1,440.0 A from another product
Three sources at 45 °C: A and B are model results for one hypothetical unit (1,600 A, 70 K rise) under two assumptions; C is another product's published table value — the three do not form a range

The first two differ by 95.63 A, or 5.977 percentage points, and the whole gap comes from the assumption itself: one holds a rise (in kelvin), the other an absolute temperature (in °C). Raise the ambient by 10 K and hold the 70 K rise: the conductor reaches 115 °C and the current falls 1.44%. Hold the conductor at 105 °C instead: the rise must fall to 60 K and the current drops 7.42%. Both are model results, not measured values.

The third row is a different object. That table lists coefficients for the manufacturer's own product: on that table, 1.00 at 35 °C becomes 0.90 at 45 °C, below both hypothetical models here. On the same page, Figure 8-4 plots the same coefficients against an axis labelled 24 h average temperature, which indicates the basis is not an instantaneous peak. How those coefficients were derived, and how much margin they carry, is not disclosed in the document; this article does not infer it.

Largest minus smallest is 136.9 A, or 8.56% of the 1,600 A nameplate. That is only the numerical difference between three illustrative figures — one model value, one value from a second model, and one other product's table value. The denominator is an illustrative nameplate figure, not any achievable operating value.

Is "0.5% per °C" correct?

The figure matches none of the evidence, and should not be treated as a constant.

Run the constant-rise model segment by segment: from 20 °C to 50 °C the reduction over each 5 K interval falls from 0.76% to 0.71%, or 0.142 to 0.152 %/K, almost independent of temperature. Switch to the constant-conductor assumption and the same model returns 0.597 to 0.851 %/K — change the constraint and the slope steepens. A steepening slope therefore tells you nothing about its cause.

Now the published table: from 35 °C upward, the segment averages run 1.000, 1.053, 1.111, 1.176, 1.500 and 1.892 %/K, so a single table spans 1.0 to 1.9 on its own.

What can be confirmed is narrow: none of these three behaves as a uniform 0.5 %/K. How much of a tabulated factor comes from deteriorating dissipation, from radiative non-linearity, or from manufacturer margin cannot be read off the shape. The fault in the sentence is treating a variable rate as a constant.

Do two busways side by side need a derating factor?

The standard text contains no coefficient for this, and side-by-side installation is exactly what a data hall does.

Clause 5.3.2 says mounting conditions may include orientation and position, with position illustrated "for example" as edgewise or flatwise, and/or below or on top of the unit for a tap-off. That is illustrative wording, not an exhaustive list. What can be confirmed is narrower: this clause gives no factor for clearance between parallel runs. It does not establish that no such factor exists in the industry, nor does it rule out a manufacturer declaring an installation correction for a specific arrangement.

Practice splits two ways: ask the manufacturer for a side-by-side factor, or borrow from cable grouping practice. The second must state its object — cable grouping rests on several cables bundled together and heating each other. A busway is a separate unit with a metal enclosure that both dissipates and blocks heat, on a different coupling path. It cannot be cited as a busway selection method.

A long row of tap-off boxes does not derate the run. Clause 5.4 sets the system diversity factor at 1 unless otherwise specified, with Note 1 giving the reason — thermal influence between tap-off units is negligible — and the run remains limited by the rated current of the trunking and feeder units. A different level must be kept separate: where one tap-off box contains several main outgoing circuits, those circuits take 0.9 (2–3), 0.8 (4–5), 0.7 (6–9) or 0.6 (10 and above) per Table 101 — values that also carry the "unless otherwise specified" premise; and the same clause states that they are loaded simultaneously within the limit of the tap-off unit's own rated current. The RDF settles simultaneity only; it does not lift that ceiling.

Which ambient temperature should a data centre use?

The design temperature at the busway's own location, not the room setpoint. In one hall the two can differ by 18 K.

Three things must be stated together: position (cold-aisle side, above the hot aisle, ceiling void, supply-air section — four different temperatures), duration (annual maximum, 24 h average, or short-term peak), and whether the situation counts as a special service condition. The manufacturer's curve plots against 24 h average temperature, which is not the same basis as a summer peak; the two are not interchangeable, and whichever you use has to match the basis the product declares.

On the model, moving from 27 °C to 45 °C takes the same unit from 1,619.2 A to 1,576.9 A under the constant-rise assumption. The higher figure exceeds the nameplate, and that only shows the model extrapolating upward below the reference point — it is not evidence that the unit may run above nameplate. The nameplate is a conditional declaration; capability below the reference point still has to come from the manufacturer.

So what should you do at selection?

Three steps, in order.

Establish the reference. Confirm which ambient, whether average or peak, which mounting direction, and whether single or side-by-side, the catalogue figure assumes. Miss one and the numbers are not comparable.

Ask for a curve, not a table. Request the full temperature-coefficient curve for the product rather than a single 0.9 or 0.85. It must cover the extremes at the project site — the published table stops at 65 °C, and some industrial ceiling voids exceed that.

Check against the product's declaration and its verification documents; do not pick a criterion yourself. Table 6 sets different limits by part (busbar, terminal, enclosure); confirm which part you are checking. The edition cited here is GB/T 7251.1-2013 — the edition 7251.6 references by date; the 2023 edition has its own Table 6 and can only serve as a comparison. The 105 K row deserves particular care: 45 °C plus 105 K is 150 °C, already above the 130 °C nominal limit of Class B. Class F nominally allows 155 °C, but that 5 K difference is not system margin — thermal class is a material property, and 105 K itself applies only when all five conditions of Note g to Table 6 hold.

One arithmetic boundary: an ambient 10 K higher is not a rise 10 K higher. On the same model, a unit with a 50 K rise, held at constant current while ambient moves from 35 °C to 45 °C, sees the rise increase only to about 51.86 K — the extra 10 K lands on the ambient. Treating the two as the same thing produces a wrong figure such as 60 K.

Open questions

No agreed side-by-side coefficient exists in public text. Clause 5.3.2 gives no clearance factor, and publicly available catalogues mostly give a single-unit curve. Judging two parallel runs currently means going back to the manufacturer or measuring on the actual installation.

The composition of a tabulated factor cannot be decomposed. Deteriorating dissipation, radiative non-linearity and manufacturer margin are folded together in one curve; shape alone cannot allocate weights.

References

All links accessed 2026-11-23.

  1. GB/T 7251.6-2015, Low-voltage switchgear and controlgear assemblies — Part 6: Busbar trunking systems (busways) — standard detail page (current; effective 2016-06-01; reviewed 2026-11-05; wholly replaces GB 7251.2-2006). https://openstd.samr.gov.cn/bzgk/std/newGbInfo?hcno=C09C8DDFAD467798FAAE736B9E97CEB1
  2. IEC 61439-6:2012, Low-voltage switchgear and controlgear assemblies — Part 6: Busbar trunking systems (busways) — public full text (Clauses 5.3.1/5.3.2, Table 101 and Clause 10.10.2.3.4 share their origin with GB/T 7251.6-2015). https://law.resource.org/pub/us/cfr/ibr/inc/iec/iec.61439-6.2012.pdf
  3. GB/T 7251.1-2023, Low-voltage switchgear and controlgear assemblies — Part 1: General rules — standard information page (current; effective 2024-03-01; wholly replaces the 2013 edition). https://www.chinesestandard.net/PDF.aspx/GBT7251.1-2023
  4. ABB. WavePro LT Busway Catalogue (1SXH3432005 EN Rev A 06-2020), printed page 10, Table 8-3: ambient-temperature factors 1.00 at 35 °C, 0.95 at 40 °C, 0.90 at 45 °C, 0.85 at 50 °C, 0.80 at 55 °C, 0.74 at 60 °C, 0.67 at 65 °C; Figure 8-4 on the same page plots against an axis labelled "Ambient temperature, 24h average temperature". https://library.e.abb.com/public/79a90821451b4c0fa2d477bce0eed333/WavePro%20LT%20Catalog%201SXH3432005_EN%20Rev%20A%2006-2020.pdf

This article is an industry observation and does not constitute procurement advice. | Updated 2026-11

On This Page · 9 sections
  1. The short answer
  2. What conditions does the 1,600 A nameplate assume?
  3. Why do three different numbers come out?
  4. Is "0.5% per °C" correct?
  5. Do two busways side by side need a derating factor?
  6. Which ambient temperature should a data centre use?
  7. So what should you do at selection?
  8. Open questions
  9. References