Technical SelectionPublished 2026.09.24

How is a busway's rated current determined? Why can't ampacity be calculated from cross-section?

A busway's rated current is declared by the manufacturer and verified by a temperature-rise test. The criterion is a set of limits in Table 6 of GB/T 7251.1, divided by location; when the cross-section changes, the result is extrapolated in proportion to the square root of cross-sectional area. This article explains the mechanism and points out a version-linkage issue: the general standard edition cited by the current busway standard was replaced in 2024.

Technical SelectionApplication TrendsPublished 2026.09.24

How Is Charging-Station Transformer Capacity Calculated, and Why Is There No Formula in the National Standard?

Charging-station standards specify power-distribution outcome constraints but not a direct capacity formula. This article calculates transformer capacity step by step using demand factor, efficiency, power factor, and allowable load factor.

Emerging TechnologyPower Markets (Behind-the-Meter Energy Storage)Published 2026.09.24

How Should Commercial and Industrial Energy Storage Be Evaluated After Fixed Time-of-Use Tariffs Are Removed?

After fixed peak and off-peak periods and spread ratios are removed, commercial and industrial storage economics must be recalculated from investment cost, cycle life, and efficiency, while separating behind-the-meter returns from grid-side capacity compensation.

Technical SelectionStandards & PolicyPublished 2026.09.24

How are harmonic-current limits allocated among multiple users? Why can't Table 2 be applied directly?

The harmonic-current allowable values in Table 2 of GB/T 14549 are the limits that all users at a point of common coupling must meet collectively, not the limit for one user. To apply them to an individual user, first convert the value using the actual minimum short-circuit capacity, then allocate it according to contracted capacity; the allocation exponent changes with harmonic order. This article explains the two-step mechanism and identifies four common errors caused by copying the table directly.

Technical SelectionPublished 2026.09.24

How Should a PE Conductor Be Sized? Table 54.2 Is Only the Minimum—Circuit Length Is Critical

Use an illustrative TN-S circuit to verify both the thermal withstand and protection sensitivity of a PE conductor. A tabulated cross-section alone does not resolve the effect of circuit length.